ProLiant ML370Maintenance and Service GuideFourth Edition (June 2000)Part Number 143091-004Spare Part Number 158549-001Compaq Computer Corporation

Pagina 2 - Spare Part Number 158549-001

Chapter 1Illustrated Parts CatalogThis chapter provides the illustrated parts breakdown and a spare parts list forCompaq ProLiant™ ML370 Servers. See

Pagina 3 - Contents

3-46 Compaq ProLiant ML370 Maintenance and Service GuideIntegrated Management LogOn servers supporting the Integrated Management Display, the Compaq

Pagina 4 - Chapter 3

Diagnostics and Troubleshooting 3-47Viewing the Event List 1. From Compaq Insight Manager, select the appropriate server, then select View DeviceDat

Pagina 5

3-48 Compaq ProLiant ML370 Maintenance and Service GuideEvent ListThe Event List displays the affected components and the associated error messages.

Pagina 6

Diagnostics and Troubleshooting 3-49Table 3-17Event Messages continuedEvent Type Event Message ActionProcessorCorrectable ErrorThreshold exceededPro

Pagina 7 - About This Guide

3-50 Compaq ProLiant ML370 Maintenance and Service GuideRapid Error RecoveryCompaq servers provide rapid recovery services for diagnosing and recove

Pagina 8 - Compaq Technician Notes

Diagnostics and Troubleshooting 3-51The available recovery features are: Software Error Recoveryautomatically restarts the server after a softwar

Pagina 9 - Telephone Numbers

3-52 Compaq ProLiant ML370 Maintenance and Service GuideHardware RequirementsTo use this level of ASR-2 over a modem, you need the following: A Co

Pagina 10 - Illustrated Parts Catalog

Diagnostics and Troubleshooting 3-53You can configure the server to start Compaq Utilities in four different ways: Without remote console support;

Pagina 11

3-54 Compaq ProLiant ML370 Maintenance and Service GuideCompaq Integrated Remote ConsoleThe standard Compaq Integrated Remote Console performs a wid

Pagina 12 - Mechanical Spare Parts List

Diagnostics and Troubleshooting 3-55The following ASR-2 flow chart shows you the sequence of events after a hardware or softwareerror occurs:Hardwar

Pagina 13

1-2 Compaq ProLiant ML370 Maintenance and Service GuideMechanical Parts Exploded View23457861Figure 1-1. Mechanical parts exploded view

Pagina 14 - System Components Spare Parts

3-56 Compaq ProLiant ML370 Maintenance and Service GuideBooting into Compaq UtilitiesWhen you enable ASR-2 to start into Compaq Utilities and a crit

Pagina 15 - Table 1-2

Diagnostics and Troubleshooting 3-57Table 3-19Compaq System Configuration Utility Pager Settings for Booting into Compaq Utilities continuedPager Da

Pagina 16

3-58 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-19Compaq System Configuration Utility Pager Settings for Booting into Compaq Utiliti

Pagina 17 - Chapter 2

Diagnostics and Troubleshooting 3-59The System Configuration Utility setting should resemble the following when you enable ASRto restart into the op

Pagina 18 - Symbols in Equipment

3-60 Compaq ProLiant ML370 Maintenance and Service GuideASR-2 Integrated Management Log MessagesThe Integrated Management Log (IML) records memory e

Pagina 19 - Preparation Procedures

Diagnostics and Troubleshooting 3-61Table 3-21ASR-2 IML Messages continuedMessage DescriptionNMI—PCI Bus Parity Error A parity error was detected on

Pagina 20 - Rack Warnings

3-62 Compaq ProLiant ML370 Maintenance and Service GuideRevision History TableSome errors can be resolved by reviewing changes to the server configu

Pagina 21

Diagnostics and Troubleshooting 3-63Storage Fault Recovery TrackingThis feature tracks over 12 failure-indication parameters, such as timeouts, spin

Pagina 22 - Front Bezel

3-64 Compaq ProLiant ML370 Maintenance and Service GuideRemote Service FeaturesCompaq servers have the following management features that you can ac

Pagina 23 - Rack Front Plate

Diagnostics and Troubleshooting 3-65ROMPaq Disaster RecoveryThe following option should be utilized by any server that does not have a valid ROM ima

Pagina 24

Illustrated Parts Catalog 1-3Mechanical Spare Parts ListTable 1-1Mechanical Spare Parts ListItem Description Spare Part NumberChassis1 Chassis 15798

Pagina 25 - Large Access Panel

3-66 Compaq ProLiant ML370 Maintenance and Service Guide 10. After successful completion of this process, a. Power down the server b. Remove the dis

Pagina 26 - Small Access Panel

Diagnostics and Troubleshooting 3-67Compaq Insight ManagerCompaq Insight Manager is the Compaq application for easily managing network devices.Compa

Pagina 27 - Right Side Panel

3-68 Compaq ProLiant ML370 Maintenance and Service Guide SNMP standards provide integration with other management products. Flexible network co

Pagina 28 - Drives and Related Components

Chapter 4Connectors, Switches, and LED IndicatorsThis chapter provides connector, switch, and LED indicator information for CompaqProLiant ML370 Serve

Pagina 29 - Cable Routing Diagrams

4-2 Compaq ProLiant ML370 Maintenance and Service GuideCompaq ProLiant ML370 System Board ComponentsSee Table 4-1 for the names of the Compaq ProLia

Pagina 30 - SCSI Cable Diagram

Connectors, Switches, and LED Indicators 4-3Rear Panel ComponentsSee Table 4-2 for the names of the Compaq ProLiant ML370 rear panel components.1234

Pagina 31 - Hot-Plug Drive Cage

4-4 Compaq ProLiant ML370 Maintenance and Service GuideSwitchesThe Compaq ProLiant ML370 Server has two switchbanks (SW1 and SW2) located on thesyst

Pagina 32

Connectors, Switches, and LED Indicators 4-5SW1 – System Identification Switch SettingsThe processor configuration switchbank (SW1) is an eight-posi

Pagina 33 - Diskette Drive

4-6 Compaq ProLiant ML370 Maintenance and Service GuideLED IndicatorsThis section contains graphics and tables showing LED indicator locations and f

Pagina 34 - Hard Drive Blank

Connectors, Switches, and LED Indicators 4-7RJ-45 ConnectorFigure 4-5 and Table 4-6 show the location and a description of the RJ-45 connector LEDin

Pagina 35 - Hot-Plug SCSI Hard Drive

1-4 Compaq ProLiant ML370 Maintenance and Service GuideSystem Components Exploded View152021a191913168221012261127a181714aFigure 1-2. System compon

Pagina 36

4-8 Compaq ProLiant ML370 Maintenance and Service GuideSystem BoardFigure 4-6 and Table 4-7 show the location and meaning of the indicators.1234 5 6

Pagina 37

Connectors, Switches, and LED Indicators 4-9Riser BoardFigure 4-7 and Table 4-8 show the location and meaning of the riser board indicator.11Figure

Pagina 38

Chapter 5Physical and Operating SpecificationsThis chapter provides operating and performance specifications for the CompaqProLiant ML370 Server compo

Pagina 39

5-2 Compaq ProLiant ML370 Maintenance and Service GuideSystem UnitTable 5-1System Unit SpecificationsDimensionsHeight (without feet) 45.52 cm (17.9

Pagina 40

Physical and Operating Specifications 5-3Power SupplyTable 5-2Power Supply SpecificationsInput specificationsRated input voltage 100 – 240 VACRated

Pagina 41 - Riser Board Expansion Slots

5-4 Compaq ProLiant ML370 Maintenance and Service GuideRedundant Power SupplyTable 5-3Redundant Power Supply SpecificationsInput specificationsRated

Pagina 42 - I/O Expansion Slot Cover

Physical and Operating Specifications 5-5Dual Inline Memory Modules (DIMM)Table 5-4DIMM SpecificationsSize 64-, 128-, 256-, 512 MB, or 1 GBSpeed 133

Pagina 43 - I/O Expansion Board

5-6 Compaq ProLiant ML370 Maintenance and Service GuideIDE CD-ROM DriveTable 5-6IDE CD-ROM Drive SpecificationsApplicable disk CD-ROM (modes 1 and 2

Pagina 44 - Riser Board and Brace

Physical and Operating Specifications 5-7Compaq Wide Ultra2 Hot-Plug SCSI Hard DrivesTable 5-7Compaq Wide Ultra2 Hot-Plug SCSI Hard Drive Specificat

Pagina 45 - Processor

5-8 Compaq ProLiant ML370 Maintenance and Service GuideIntegrated Dual Channel SCSI ControllerTable 5-8Integrated Dual Channel SCSI Controller Speci

Pagina 46 - Processor Power Module

Illustrated Parts Catalog 1-5System Components Spare PartsTable 1-2System Components Spare Parts ListItem Description Spare Part NumberSystem Compon

Pagina 47 - SDRAM DIMM Slot Locations

IndexAaccess panelslarge accesspart number 1-3removing 2-9removing, illustrated 2-9replacing 2-9right sidepart number 1-3removing 2-11remo

Pagina 48

2 Compaq ProLiant ML370 Maintenance and Service Guidesoftware errorrecovery 3-53recovery boot option 3-53recovery time-out 3-53standby recover

Pagina 49

Index 3remote maintenance 3-68viewing the event list 3-47Compaq Integrated Remote Consolefeatures 3-54Compaq Integrated Smart ArrayControllerl

Pagina 50

4 Compaq ProLiant ML370 Maintenance and Service Guidetransporting parts safely 2-2workstationrecommendations 2-2environmental recovery 3-51err

Pagina 51 - Hot-Plug SCSI Drive Backplane

Index 5correctable errorthreshold exceeded 3-48,3-49Diagnostic Error 3-60dirty data 3-36disable command issued 3-39drive (bay)drive X failed

Pagina 52

6 Compaq ProLiant ML370 Maintenance and Service Guidepower AC overload 3-49power modulefailure 3-49not redundant 3-49power supplyfailure 3-4

Pagina 53

Index 7Compaq Integrated Smart ArrayController upgrade module,removing 2-37CPU fan, removing 2-21DIMM slots on systemboard 2-31diskette drive,

Pagina 54 - Internal Replacement Battery

8 Compaq ProLiant ML370 Maintenance and Service Guidetest error codes 3-29kitsdata cable, part number 1-5hardware, part number 1-6plastics, pa

Pagina 55

Index 9right sidepart number 1-3removing 2-11removing, illustrated 2-11replacing 2-11small accesspart number 1-3removing 2-10removing, i

Pagina 56 - Diagnostic Tools

10 Compaq ProLiant ML370 Maintenance and Service GuideRrack conversion kit, part number 1-6rack front plate See front platerack warnings 2-4Ra

Pagina 57

1-6 Compaq ProLiant ML370 Maintenance and Service GuideTable 1-2System Components Spare Parts List continuedItem Description Spare Part NumberCables

Pagina 58 - Default Configuration

Index 11standby recoveryserver option 3-53server port 3-53time-out 3-53static electricity See electrostaticdischargestorage automatic recons

Pagina 59 - Utilities Access

12 Compaq ProLiant ML370 Maintenance and Service GuideRiser Board ExpansionSlots 2-25Riser Board LED Indicator 4-9RJ-45 Connected LEDIndicators

Pagina 60 - Software CD

Index 13Firmware Upgrade,accessing 3-5Health Driver 3-54IML Management utility,defined 3-47Inspectaccessing 3-2, 3-26description 3-2, 3-4p

Pagina 61 - Power-On Self-Test (POST)

Illustrated Parts Catalog 1-7Table 1-2System Components Spare Parts List continuedItem Description Spare Part NumberOptions continued42 9.1-GB, 1-in

Pagina 62 - POST Error Messages

Chapter 2Removal and Replacement ProceduresThis chapter provides subassembly/module-level removal and replacement procedures forCompaq ProLiant ML370

Pagina 63

2-2 Compaq ProLiant ML370 Maintenance and Service GuideElectrostatic Discharge InformationA discharge of static electricity can damage static-sensit

Pagina 64

Removal and Replacement Procedures 2-3Weight in kgWeight in lbAny product or assembly marked with these symbols indicates that thecomponent exceeds

Pagina 65

NoticeThe information in this publication is subject to change without notice.COMPAQ COMPUTER CORPORATION SHALL NOT BE LIABLE FOR TECHNICAL OREDITORIA

Pagina 66

2-4 Compaq ProLiant ML370 Maintenance and Service GuideWARNING: To reduce the risk of personal injury or damage to the equipment: If the server ism

Pagina 67

Removal and Replacement Procedures 2-5Server Warnings and PrecautionsWARNING: To reduce the risk of personal injury from hot surfaces, allow the in

Pagina 68

2-6 Compaq ProLiant ML370 Maintenance and Service GuideFront BezelNOTE: This procedure applies to the ProLiant ML370 tower model only.To open the f

Pagina 69

Removal and Replacement Procedures 2-7Rack Front PlateNOTE: This procedure applies to the ProLiant ML370 rack-mountable model only.To remove the ra

Pagina 70

2-8 Compaq ProLiant ML370 Maintenance and Service GuideFeetNOTE: This procedure applies to the ProLiant ML370 tower model only.To remove the feet f

Pagina 71

Removal and Replacement Procedures 2-9Large Access PanelWARNING: To reduce the risk of personal injury from hot surfaces, allow internal systemcomp

Pagina 72

2-10 Compaq ProLiant ML370 Maintenance and Service GuideSmall Access PanelWARNING: To reduce the risk of personal injury from hot surfaces, allow i

Pagina 73

Removal and Replacement Procedures 2-11Right Side PanelNOTE: This panel does not exist on the rack-mountable model. This procedure applies to the t

Pagina 74

2-12 Compaq ProLiant ML370 Maintenance and Service GuideDrives and Related ComponentsCompaq ProLiant ML370 Servers ship standard with a hot-plug dri

Pagina 75

Removal and Replacement Procedures 2-13Cable Routing DiagramsCAUTION: When routing cables, always ensure that the cables are not in a position wher

Pagina 76

ContentsAbout This GuideSymbols in Text...viiCom

Pagina 77

2-14 Compaq ProLiant ML370 Maintenance and Service GuideSCSI Cable Diagram1122Figure 2-10. SCSI cable diagram: the three-device, terminated SCSI

Pagina 78

Removal and Replacement Procedures 2-15Hot-Plug Drive CageTo remove the hot-plug drive cage: 1. Perform the preparation procedures. See “Powering D

Pagina 79

2-16 Compaq ProLiant ML370 Maintenance and Service GuideIDE CD-ROM DriveTo remove the CD-ROM drive: 1. Perform the preparation procedures. See “Pow

Pagina 80 - Diagnostics Software

Removal and Replacement Procedures 2-17Diskette DriveTo remove the diskette drive: 1. Perform the preparation procedures. See “Powering Down the Se

Pagina 81 - Table 3-3

2-18 Compaq ProLiant ML370 Maintenance and Service GuideHard Drive BlankIMPORTANT: A hard drive blank must be installed in an unused hard drive slo

Pagina 82 - Memory Test Error Codes

Removal and Replacement Procedures 2-19Hot-Plug SCSI Hard DriveTo remove a hot-plug SCSI hard drive: 1. Open the front bezel (tower model only). Se

Pagina 83 - Table 3-6

2-20 Compaq ProLiant ML370 Maintenance and Service GuideRemovable Media Drive Bay BlankTo remove a removable media drive bay blank: 1. Open the fro

Pagina 84 - Table 3-7

Removal and Replacement Procedures 2-21CPU FanTo remove the CPU fan: 1. Perform the preparation procedures. See “Powering Down the Server” earlier

Pagina 85 - Serial Test Error Codes

2-22 Compaq ProLiant ML370 Maintenance and Service GuideI/O FanTo remove the I/O fan: 1. Perform the preparation procedures. See “Powering Down the

Pagina 86 - Table 3-11

Removal and Replacement Procedures 2-23Power Switch with Cable and LED IndicatorsTo remove the power switch and cable assembly: 1. Perform the prep

Pagina 87 - Table 3-13

iv Compaq ProLiant ML370 Maintenance and Service GuideRemoval and Replacement ProcedurescontinuedI/O Fan...

Pagina 88 - Table 3-15

2-24 Compaq ProLiant ML370 Maintenance and Service Guide 6. Disconnect the power switch from the system board . 4Figure 2-20. Unplugging the powe

Pagina 89 - Starting ADU

Removal and Replacement Procedures 2-25Riser Board Expansion Slots23456123456Figure 2-21. Riser board expansion slotsTable 2-2Riser Board Expansion

Pagina 90 - ADU Diagnostic Messages

2-26 Compaq ProLiant ML370 Maintenance and Service GuideI/O Expansion Slot CoverTo remove an I/O expansion slot cover: 1. Perform the preparation p

Pagina 91

Removal and Replacement Procedures 2-27I/O Expansion BoardTo remove an I/O expansion board: 1. Perform the preparation procedures. See “Powering Do

Pagina 92

2-28 Compaq ProLiant ML370 Maintenance and Service GuideRiser Board and BraceTo remove the riser board and brace: 1. Perform the preparation proced

Pagina 93

Removal and Replacement Procedures 2-29ProcessorTo remove the processor: 1. Perform the preparation procedures. See “Powering Down the Server” earl

Pagina 94

2-30 Compaq ProLiant ML370 Maintenance and Service GuideProcessor Power ModuleTo remove the Processor Power Module: 1. Perform the preparation proc

Pagina 95

Removal and Replacement Procedures 2-31MemoryCompaq ProLiant ML370 Servers ship standard with a 128-MB Synchronous DRAM(SDRAM) dual inline memory mo

Pagina 96

2-32 Compaq ProLiant ML370 Maintenance and Service GuideTo remove an SDRAM DIMM: 1. Perform the preparation procedures. See “Powering Down the Serv

Pagina 97

Removal and Replacement Procedures 2-33Power SupplyWARNING: To reduce the risk of electric shock, do not disassemble the power supply orattempt to

Pagina 98

Contents vDiagnostics and TroubleshootingcontinuedRemote Service Features ...

Pagina 99

2-34 Compaq ProLiant ML370 Maintenance and Service Guide 6. Disconnect all other power supply cables. 7. Remove the four Torx T-15 screws securing

Pagina 100 - Integrated Management Log

Removal and Replacement Procedures 2-35Hot-Plug SCSI Drive BackplaneTo remove the hot-plug SCSI drive backplane: 1. Perform the preparation procedu

Pagina 101 - Compaq IML Management Utility

2-36 Compaq ProLiant ML370 Maintenance and Service GuideSystem BoardTo remove the system board: 1. Perform the preparation procedures. See “Powerin

Pagina 102 - Event Messages

Removal and Replacement Procedures 2-37Compaq Integrated Smart Array Controller UpgradeModuleNOTE: The Compaq Integrated Smart Array Controller upg

Pagina 103 - Table 3-17

2-38 Compaq ProLiant ML370 Maintenance and Service GuideInternal Replacement BatteryWARNING: This server contains an internal lithium manganese dio

Pagina 104 - Rapid Error Recovery

Chapter 3Diagnostics and TroubleshootingThis chapter describes software and firmware diagnostic tools available for all Compaq serverproducts. The sec

Pagina 105 - Attended Recovery

3-2 Compaq ProLiant ML370 Maintenance and Service GuideDiagnostic Tools Utility OverviewThese utilities were developed to assist in diagnosing probl

Pagina 106 - Hardware Requirements

Diagnostics and Troubleshooting 3-3Table 3-1Diagnostic Tools continuedTool What it is How to run itArray DiagnosticsUtility (ADU)A Windows-based too

Pagina 107 - ASR-2 Features

3-4 Compaq ProLiant ML370 Maintenance and Service GuideDefault ConfigurationWhen the system is first powered up, the system ROM detects the unconfig

Pagina 108 - Compaq Health Driver

Diagnostics and Troubleshooting 3-5Utilities AccessThe Compaq SmartStart and Support Software CD contains the SmartStart program and manyof the Comp

Pagina 110 - Table 3-19

3-6 Compaq ProLiant ML370 Maintenance and Service GuideRunning the Utilities from Diskette Run the utilities from their individual diskettes. If y

Pagina 111

Diagnostics and Troubleshooting 3-7Power-On Self-Test (POST)POST is a series of diagnostic tests that run automatically on Compaq computers when the

Pagina 112

3-8 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error MessagesError Code Audible Beeps Probable Source of Problem Recommended A

Pagina 113 - ASR-2 Security

Diagnostics and Troubleshooting 3-9Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action175 -

Pagina 114 - ASR-2 IML Messages

3-10 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 115

Diagnostics and Troubleshooting 3-11Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended ActionZZ-3

Pagina 116 - Table 3-22

3-12 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 117

Diagnostics and Troubleshooting 3-13Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1702

Pagina 118 - ROMPaq Error Recovery Options

3-14 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 119 - ROMPaq Disaster Recovery

Diagnostics and Troubleshooting 3-15Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1731

Pagina 120 - b. Remove the diskette

About This GuideThis maintenance and service guide is a troubleshooting guide that can be used for referencewhen servicing Compaq ProLiant ML370 Serve

Pagina 121 - Compaq Insight Manager

3-16 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 122 - Insight Management Agents

Diagnostics and Troubleshooting 3-17Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1774

Pagina 123 - Chapter 4

3-18 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 124 - System Board Components

Diagnostics and Troubleshooting 3-19Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1778

Pagina 125 - Rear Panel Components

3-20 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 126 - Switches

Diagnostics and Troubleshooting 3-21Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1786

Pagina 127 - Table 4-4

3-22 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 128 - LED Indicators

Diagnostics and Troubleshooting 3-23Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1789

Pagina 129 - RJ-45 Connector

3-24 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Re

Pagina 130 - System Board

Diagnostics and Troubleshooting 3-25Table 3-2POST Error Messages continuedError Code Audible Beeps Probable Source of Problem Recommended Action1797

Pagina 131 - Riser Board

viii Compaq ProLiant ML370 Maintenance and Service GuideCompaq Technician NotesWARNING: Only authorized technicians trained by Compaq should attemp

Pagina 132 - Chapter 5

3-26 Compaq ProLiant ML370 Maintenance and Service GuideDiagnostics SoftwareTest Error Codes Tables include all test error codes generated by Compaq

Pagina 133 - System Unit

Diagnostics and Troubleshooting 3-27100-199, Primary Processor Test Error CodesThe 100 series of diagnostic error codes identifies failures with pro

Pagina 134 - Power Supply

3-28 Compaq ProLiant ML370 Maintenance and Service Guide200-299, Memory Test Error CodesThe 200 series of diagnostic error codes identifies failures

Pagina 135 - Redundant Power Supply

Diagnostics and Troubleshooting 3-29300-399, Keyboard Test Error CodesThe 300 series of diagnostic error codes identifies failures with keyboard and

Pagina 136 - 1.44-MB Diskette Drive

3-30 Compaq ProLiant ML370 Maintenance and Service Guide500-599, Graphics Controller Unit Test Error CodesThe 500 series of diagnostic error codes i

Pagina 137 - IDE CD-ROM Drive

Diagnostics and Troubleshooting 3-31600-699, Diskette Drive Test Error CodesThe 600 series of diagnostic error codes identifies failures with disket

Pagina 138 - Table 5-7

3-32 Compaq ProLiant ML370 Maintenance and Service Guide1200-1299, Modem Communications Test Error CodesThe 1200 series of diagnostic error codes id

Pagina 139 - Table 5-8

Diagnostics and Troubleshooting 3-336500-6599, SCSI Hard Drive Test Error CodesThe 6500 series of diagnostic error codes identifies failures with SC

Pagina 140

3-34 Compaq ProLiant ML370 Maintenance and Service Guide6700-6799, SCSI Tape Drive Test Error CodesThe 6700 series of diagnostic error codes identif

Pagina 141

Diagnostics and Troubleshooting 3-35Array Diagnostic Utility (ADU)Array Diagnostic Utility (ADU) is a Windows-based software tool designed to run on

Pagina 142

About This Guide ixIntegrated Management DisplaySome Compaq server models include a Compaq Integrated Management Display (IMD), anintegrated, 16 × 4

Pagina 143

3-36 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-16ADU Diagnostic MessagesMessage Description Recommended ActionAcceleratorboard notd

Pagina 144

Diagnostics and Troubleshooting 3-37Table 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionAcceleratorstatus: ExcessiveECC

Pagina 145

3-38 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionAdapter/NVR

Pagina 146

Diagnostics and Troubleshooting 3-39Table 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionController is notconfiguredIf c

Pagina 147

3-40 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionDrive (bay)

Pagina 148

Diagnostics and Troubleshooting 3-41Table 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionError occurredreading RIS copyf

Pagina 149

3-42 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionLogical Dri

Pagina 150

Diagnostics and Troubleshooting 3-43Table 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionLoose cabledetected—logical dri

Pagina 151

3-44 Compaq ProLiant ML370 Maintenance and Service GuideTable 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionSCSI Port x

Pagina 152

Diagnostics and Troubleshooting 3-45Table 3-16ADU Diagnostic Messages continuedMessage Description Recommended ActionWarning bitdetectedA monitor an

Comentarios a estos manuales

Sin comentarios