Compaq J4367A - UPS R3000 XR Manual de usuario Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 71
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
HP IT-Symposium 2006
29www.decus.de
5/16/2006 57
BACK TO START/AGENDA
HP MCS – Aufstell Optionen
Draufsicht
5/16/2006 58
BACK TO START/AGENDA
HP MCS - Tech Specs Overview (1/2)
Cooling capacity (dependent on water in take temperature and flow rate): 30KW
Chilled air plenum placed in front of the servers: 2750 CFM (4650 m
3
/h)
Air Temperature to servers: free configurable / recommendation: 25°C
Automatic system regulation cycle (load based)
42U free rack space in the rack - for server and storage equipment
3 Hot swap heat exchanger and fans
3 Hot swap fans
Dimensions & Weight
Dimensions (over all), H x W x D: ~ 2000mm x 909mm x 1270mm
compared to a standard HP universal rack (42U):
width: + 317 mm; depth: +~ 270 mm
Weight (net/unpacked, Rack + Cooling unit): 513 kg
IT Rack equipment cable feed (power, network): Top & Bottom cable egree
Vista de pagina 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 70 71

Comentarios a estos manuales

Sin comentarios