Compaq J4367A - UPS R3000 XR Manual de usuario Pagina 30

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 71
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 29
HP IT-Symposium 2006
30www.decus.de
5/16/2006 59
BACK TO START/AGENDA
HP MCS - Tech Specs Overview (2/2)
Water
Water connection: Parker Hannifin 1¼” 6100 Series
Flexible hose length (pre-installed), bottom: 914 mm
Water flow rate: 10 - 76 (max.) Liter per minute
Water pressure: ~ 1,5 Bar
Water temperature for incoming water: ~10°C (min.: 5°C)
Condensate evacuation system (condensat tube & tray, sensors, pump, line)
Power
power input redundancy: redundant power in (2x)
power connector: 2 x IEC 309 (16A); power feed at the bottom
power usage: ~ 1500 Watts (full load)
Integrated system monitoring
Local display - Multi-function LCD status and control console
embedded – Web management interface
SIM 5.0 Integration: SNMP traps and browser launch
Sensors: Temp air front of servers, temp of water in, water flow, humidity, leakage,
fan speed, …
5/16/2006 60
BACK TO START/AGENDA
HP MCS – Prüfzeichen und Tests
UL Listing 484
CUL Canadian std. 22.2 No.236
CB report to IEC 60950-1
TÜV DIN 3168, GS EN 60335-1 (according to 60335-2-40)
TÜV Prüfbedingungen / nach zwei Stunden kein Kondensat im Serverrack
bei: 80% rel. Luftfeuchte
30 °C Umgebungs-Temperatur
10 °C Wasservorlauf-Temperatur
Mit 15 Bar getestet! (Produktionskontrolle)
Betriebsdruck: ca. 1,5 Bar
Vista de pagina 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 70 71

Comentarios a estos manuales

Sin comentarios