HP IT-Symposium 2006
31www.decus.de
5/16/2006 61
BACK TO START/AGENDA
HP MCS –
ROIT / Yearly Savings Calculation
Datacenter Operating cost per sq meter pa 13.500 €
kW per rack kW per rack
conventional air
cooling
MCS
cooling
Area per conventional rack (Burdened) sq meter 2,32
Average kW deployed per 42U rack 6,00 24,00
Amount of conventional racks 4,00
Area needed to cool with conventional cooling / sq meter 9,29
Area per MCS (30kW capacity) (Burdened) sq meter 3,25
Saved sq meter with MCS (total)
6,04
Yearly Savings per MCS unit (based on space savings) 81.522 €
Costs per MCS (unit + infrastructure) + operating costs pa 35.600 €
ROIT (Yearly costs / savings) * 12 month
5,24
month!Break even after
Type in
your value!
Type in
your value!
Get your
result here!
Type in
your value!
5/16/2006 62
BACK TO START/AGENDA
Why buy HP MCS (Zusammenfassung)
Bis 30 kW Kühlkapazität – oder: 20 kW mit n+1 Redundanz
spart Platz im Rechenzentrum - Stellfläche: ca. 1,13 qm; -> ca. 26 kW pro
qm
volle 42 HE für IT Equipment bei Standard-Rackhöhe (42 HE bzw. 2 Meter)
Gleichmässige Kühlung über die gesamte Rackhöhe durch Side Airflow
Design
Hohe System-Effizienz durch inteligente Regelung
Hohe Verfügbarkeit durch umfangreiche Redundanz- & Sicherheits-
Funktionen
Keine Unterbrechung vom Kühlkreislauf - auch bei geöffneten Türen
Jeweils drei hot plug Lüfter- & Wärmetauscher-Module
Im HP Systemumfeld zertifiziert (mit Server, Storage und Management-
Software getestet und integriert)
HP MCS Monitoring und Management in HP SIM integriert